![Siemens SIRIUS 3RH Series Скачать руководство пользователя страница 148](http://html.mh-extra.com/html/siemens/sirius-3rh-series/sirius-3rh-series_system-manual_383139148.webp)
SIRIUS 3RT2 contactors/contactor assemblies
2.5 Mounting
SIRIUS Innovations
148
System Manual, 01/2011, A8E56203870002-03
2.5
Mounting
2.5.1
Mounting
2.5.1.1
Mounting options
Note the following information when mounting contactors:
●
If foreign bodies (such as drillings) can reach the devices, the contactors must be
covered during mounting.
●
If there is a risk of pollution, heavy dust deposits, or an aggressive atmosphere at the
mounting location, the contactors must be installed in an enclosure.
●
Dust deposits must be vacuumed away.
Mounting options
The following mounting types are available for contactors in sizes S00 and S0:
●
Snapping onto a 35 mm DIN rail according to DIN EN 60715.
●
Screwing onto a mounting plate
2.5.1.2
Mounting position
The contactors are dimensioned for operation on a vertical mounting plane. The following
mounting positions are permitted:
Table 2- 18 Permissible mounting positions for the contactors
Mounting positions for sizes S00 and S0
r
r
r
Note
A lateral distance from grounded parts of over 6 mm must be observed.
Vertical mounting
A special version of the 3RH2 contactor relays and 3RT2 power contactors is required for
vertical mounting. This special version can be requested from Technical Assistance
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......