Technical data
11.3 3RU21 thermal overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
118
Manual, 09/2014, A5E03656507420A/RS-AA/002
11.3.2.2
Main circuit
Technical data for the main circuit, 3RU2136 overload relays
3RU2136-....
Insulation voltage with degree of pollution 3 rated value V
690
Impulse voltage resistance rated value
kV
6
Operating voltage rated value
V
690
Voltage type for main circuit
AC/DC
Operating frequency
•
rated value
Hz
50 … 60
Type of assignement
2
Derating factor for rated value of the operating current
up to 60 °C interior cabinet temperature
1
Derating factor for rated value of the operating current
up to 70 °C interior cabinet temperature
0.87
11.3.2.3
Main circuit terminals
Technical data for main circuit connection, 3RU2136 overload relays
3RU2136-....
Arrangement of electrical connectors for main current
circuit
Top and bottom
Design of the electrical connection for main current
circuit
screw-type terminals
Type of the connectable conductor cross-section
•
for main contacts
–
solid or multi-stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
–
finely stranded with conductor end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
•
for AWG conductors for main contacts
2x (18 ... 2), 1x (18 ... 1)
Tightening torque for main contacts with screw-type
terminals
N·m 3 … 4.5
Design of the thread of the connection screw for main
contacts
M6
Design of screwdriver shaft
5 to 6 mm diameter
size of screwdriver tip
Pozidriv PZ 2