Standard mapping 3-2
3-3
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
3.1.3
Registers 00027 to 00030: Double commands
•
User-defined double commands and associated checkback indications as double-
point indications can be routed on these positions as “Source/Destination system
interface” using the
DIGSI Configuration matrix
.
•
Please ref. to chap. “Double command / Double-point indication” in the manual
“SIPROTEC Communication module, Modbus - Communication profile” for addi-
tional notes.
•
Registers 00027 to 00030 are available with 7UM62 V4.10 or higher.
3.1.4
Registers 00257 to 00264: Exception Flags
•
Registers are write-protected.
1
•
The contents of these registers are also readable using function "Read Exception
Status" (function code 7).
•
Installation-specific SIPROTEC objects can be routed on these register positions
using parameterization system DIGSI.
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
00027
<user-defined> ON
not pre-allocated
-
00028
<user-defined> OFF
00029
<user-defined> ON
not pre-allocated
-
00030
<user-defined> OFF
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
00257
<user-defined>
not pre-allocated
-
00258
<user-defined>
not pre-allocated
-
00259
<user-defined>
not pre-allocated
-
00260
<user-defined>
not pre-allocated
-
00261
<user-defined>
not pre-allocated
-
00262
<user-defined>
not pre-allocated
-
00263
<user-defined>
not pre-allocated
-
00264
<user-defined>
not pre-allocated
-
Содержание SIPROTEC4 7UM62
Страница 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Страница 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...