Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-8
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
11/2
Rotor locked
1 = Rotor locked
6822
11/3
START-SUP pu
1 = Startup supervision Pickup
6823
3.2.1.14 Trip coil monitor
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
11/4
FAIL: Trip cir.
1 = 74TC Failure trip circuit
6865
3.2.1.15 Cold load pickup
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
11/5
CLP OFF
1 = Cold-load-pickup is switched OFF
1994
11/6
CLP BLOCKED
1 = Cold-load-pickup is BLOCKED
1995
11/7
CLP running
1 = Cold-load-pickup is RUNNING
1996
12/0
Dyn set. ACTIVE
1 = Dynamic settings are ACTIVE
1997
3.2.1.16 Measurement supervision
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
12/1
Fail I Superv.
1 = Failure: General current supervision
161
12/2
Failure <Sum>I
1 = Failure: Current summation
162
12/3
Fail Ph. Seq.
1 = Failure: Phase sequence
171
12/4
MeasSup OFF
1 = Measurement supervision is switched OFF
197
3.2.1.17 Set point alarms
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
12/5
SP. Op Hours>
1 = Set point operating hours
272
12/6
SP. IA dmd>
1 = Set point phase A dmd>
273
12/7
SP. IB dmd>
1 = Set point phase B dmd>
274
13/0
SP. IC dmd>
1 = Set point phase C dmd>
275
13/1
SP. I1 dmd>
1 = Set point positive sequence I1 dmd>
276
13/2
SP. |Pdmd|>
1 = Set point |Pdmd|>
277
13/3
SP. |Qdmd|>
1 = Set point |Qdmd|>
278
13/4
SP. |Sdmd|>
1 = Set point |Sdmd|>
279
13/5
SP. 37-1 alarm
1 = Set point 37-1 Undercurrent alarm
284
13/6
SP. PF(55)alarm
1 = Set point 55 Power factor alarm
285
13/7
<reserved>
–
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...