Standard mapping 2-2
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
3-5
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
2/3
Input channel 3 (UsrSpO/O11)
Single-point indication ON/OFF
–
2/4
Input channel 4 (UsrSpO/O12)
Single-point indication ON/OFF
–
2/5
Input channel 5 (UsrSpO/O13)
Single-point indication ON/OFF
–
2/6
Input channel 6 (UsrSpO/O14)
Single-point indication ON/OFF
–
2/7
Input channel 7 (UsrSpO/O32)
Tagging / Internal single-point indication ON/OFF
–
3.2.1.4
Application logic CFC
•
Ref. to chap. 1.6 for additional notes.
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
3/0
CFC-Output indication 1
(UsCfcSpO1)
Single-point indication ON/OFF,
released as CFC output
–
3/1
CFC-Output indication 2
(UsCfcSpO2)
Single-point indication ON/OFF,
released as CFC output
–
3/2
CFC-Output indication 3
(UsCfcSpO3)
Single-point indication ON/OFF,
released as CFC output
–
3/3
CFC-Output indication 4
(UsCfcSpO4)
Single-point indication ON/OFF,
released as CFC output
–
3/4
CFC-Output indication 5
(UsCfcSpO5)
Single-point indication ON/OFF,
released as CFC output
–
3/5
CFC-Output indication 6
(UsCfcSpO6)
Single-point indication ON/OFF,
released as CFC output
–
3/6
CFC-Output indication 7
(UsCfcSpO7)
Single-point indication ON/OFF,
released as CFC output
–
3/7
CFC-Output indication 8
(UsCfcSpO8)
Single-point indication ON/OFF,
released as CFC output
–
4/0
CFC-Output indication 9
(UsCfcSpO9)
Single-point indication ON/OFF,
released as CFC output
–
4/1
CFC-Output indication 10
(UsCfcSpO10)
Single-point indication ON/OFF,
released as CFC output
–
4/2
CFC-Output indication 11
(UsCfcSpO11)
Single-point indication ON/OFF,
released as CFC output
–
4/3
CFC-Output indication 12
(UsCfcSpO12)
Single-point indication ON/OFF,
released as CFC output
–
4/4
CFC-Output indication 13
(UsCfcSpO13)
Single-point indication ON/OFF,
released as CFC output
–
4/5
CFC-Output indication 14
(UsCfcSpO14)
Single-point indication ON/OFF,
released as CFC output
–
4/6
CFC-Output indication 15
(UsCfcSpO15)
Single-point indication ON/OFF,
released as CFC output
–
4/7
CFC-Output indication 16
(UsCfcSpO16)
Single-point indication ON/OFF,
released as CFC output
–
3.2.1.5 Diagnosis
•
Ref. to chap. 1.5.5 and 1.5.6 for additional notes regarding "Error with a summary alarm" and "Alarm summary
event".
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
5/0
Device OK
1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart
51
5/1
ProtActive
1 = At least one protection function is active
52
5/2
Settings Calc.
1 = Setting calculation is running
70
5/3
Error Sum Alarm
1 = Error with a summary alarm ON
140
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...