Data in the PROFIBUS-DP messages
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
1-6
1.4
Configuration data of the standard mappings 2-1 to 2-4
There are three standard mappings (standard mapping 2-1 to standard
mapping 2-4) available for the SIPROTEC devices 7SJ61...7SJ63,
7SJ65, 6MD63 for parameterization with DIGSI version 4.2 or higher
which differ in the data size of the PROFIBUS-DP messages.
Standard
mapping 2-1
The standard mapping 2-1 contains:
Output direction:
•
7 double-point commands
•
29 single-point commands
Input direction:
•
7 double-point indications
•
146 single-point indications,
•
25 measured values (integer)
•
6 metered measureands (unsigned long)
•
Fault locator: Fault location (integer)
•
Counter of operating hours (unsigned long)
Standard
mapping 2-2
The standard mapping 2-2 contains:
Output direction:
•
7 double-point commands
•
29 single-point commands
Input direction:
•
7 double-point indications
•
114 single-point indications
•
10 measured values (integer)
•
2 metered measurands (unsigned long)
•
Counter of operating hours (unsigned long)
Standard
mapping 2-3
The standard mapping 2-3 contains:
Output direction:
•
8 double-point commands
•
24 single-point commands
Input direction:
•
8 double-point indications
•
64 single-point indications
•
21 measured values (integer)
•
6 metered measurands (unsigned long)
•
Counter of operating hours (unsigned long)
Содержание SIPROTEC4 6MD63
Страница 6: ...Revision index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 iv ...
Страница 56: ...Standard mapping 2 3 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 4 10 ...
Страница 62: ...Standard mapping 2 4 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 5 16 ...
Страница 64: ...Glossary 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 6 2 ...
Страница 66: ...Index 7SJ61 7SJ63 7SJ65 6MD63 PROFIBUS DP Bus mapping C53000 L1840 B006 02 7 2 ...