Technical Data
4.20 Frequency Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
623
4.20
Frequency Protection (optional)
Frequency Elements
Pick-up Values
Times
Dropout Frequency
Operating Range
Tolerances
Quantity
4, depending on setting effective on f< or f>
f> or f< adjustable for each element
For f
N
= 50 Hz
45.50 Hz to 54.50 Hz
Increments 0.01 Hz
For f
N
= 60 Hz
55.50 Hz to 64.50 Hz
Increments 0.01 Hz
Pickup times f>, f<
Approx. 85 ms
Dropout times f>, f<
Approx. 30 ms
Delay times T
0.00 s to 600.00 s
Increments 0.01 s
The set times are pure delay times.
Note on dropout times:
Dropout was enforced by current = 0 A and voltage = 0 V.
Enforcing the dropout by means of a frequency change below the dropout threshold extends the dropout times.
Δ
f = | pickup value – dropout value |
Approx. 20 mHz
In voltage range
Approx. 0.65 · U
N
up to 230 V (phase-phase)
In frequency range
25 Hz to 70 Hz
Frequencies f>, f< in specific range (f
N
±
10 %)
15 mHz in range U
LL
: 50 V to 230 V
Time delays T(f<, f>)
1 % of setting value or 10 ms
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...