Functions
2.17 Automatic Reclosure Function (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
337
Configuration of auto-reclosure
This configuration concerns the interaction between the protection and supplementary functions of the device
and the automatic reclosure function. Here, you can determine which functions of the device should start the
automatic reclosure and which not.
For the functions which should start the auto-reclosure function, the corresponding address is set to
YES
, for
the others to
NO
. The other functions cannot start the automatic reclosure because reclosure is not reasonable
here.
Forced Three-Pole Trip
If a blocking of the auto-reclosure occurs during the dead time of a 1-pole cycle without a previous 3-pole trip
command, the circuit breaker remains open at one pole. With address
3430
AR TRIP 3pole
it is possible to
determine that the tripping logic of the device issues a 3-pole trip command in this case (pole discrepancy pre-
vention for the CB poles). Set this address to
YES
if the CB can be tripped 1-pole and if it has no pole discrep-
ancy protection. Nevertheless, the device pre-empts the pole discrepancy supervision of the CB because the
forced 3-pole trip of the device is immediately initiated as soon as the reclosure is blocked following a 1-pole
trip or if the CB auxiliary contacts report an implausible circuit breaker state (see also Section 2.17 at margin
heading „Processing the circuit breaker auxiliary contacts“). The forced 3-pole trip is also activated when only
3-pole cycles are allowed, but a 1-pole trip is signalled externally via a binary input.
The forced 3-pole trip is unnecessary if only a common 3-pole control of the CB is possible.
Dead line check
Under address
3431
the dead line check can be switched active. It presupposes that voltage transformers are
installed on the line side of the feeder and connected to the device. If this is not the case or the function is not
used, set
DLC / RDT
=
WITHOUT
.
DLC / RDT
=
DLC
means that the dead line check of the line voltage is used. It only allows reclosing after it
has been verified in advance that the line is dead. In this case, the phase-to-earth voltage limit is set in address
3441
U-dead<
below which the line is considered voltage-free (disconnected). The setting is applied in volts
secondary. This value can be entered as a primary value when parameterising with a PC and DIGSI. Address
3438
T U-stable
determines the measuring time available for determining the no-voltage condition. Address
3440
is irrelevant here.
Adaptive dead time (ADT)
When operating with adaptive dead time, it must be ensured in advance that
one
end per line operates with
defined dead times and has an infeed. The other (or the others in multi-branch lines) may operate with adaptive
dead time. It is essential that the voltage transformers are located on the line side of the circuit breaker. Details
about this function can be found in Section 2.17 at margin heading „Adaptive Dead Time (ADT) and Close
Command-transfer (Remote-CLOSE)“.
Address 3420
AR WITH DIFF, i.e. with differential protection
Address 3421
AR w/ SOTF-O/C, i.e. with high-current switch-onto-fault function
Address 3422
AR w/ DIST., i.e. with distance protection
Address 3423
AR WITH I.TRIP, i.e. with permissive underreach transfer trip (PUTT)
Address 3424
AR w/ DTT, i.e. with externally fed trip command
Address 3425
AR w/ BackUpO/C, i.e. with time overcurrent protction
Address 3426
AR w/ W/I, i.e. with weak-infeed tripping
Address 3427
AR w/ EF-O/C, i.e. with earth fault protection for earthed systems
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...