Functions
2.9 Teleprotection for Earth Fault Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
263
It is absolutely necessary that the transient blocking time
TrBlk BlockTime
(address
3210
) is longer than
the duration of transients resulting from the inception or clearance of external earth faults. The send signal is
delayed by this time with the permissive overreach schemes
Dir.Comp.Pickup
and
UNBLOCKING
if the pro-
tection had initially detected a reverse fault. In the blocking scheme, the blocking of the stage release is pro-
longed by this time by both the detection of a reverse fault and the (blocking) received signal. After expiration
of
TrBlk BlockTime
(address
3210
) the delay time
Release Delay
(address
3208
) is restarted. Since the
blocking scheme always requires setting the delay time
Release Delay
, the transient blocking time
TrBlk
BlockTime
(address
3210
) can usually be set very short.
When the teleprotection schemes of the distance protection and earth fault protection share the same channel,
EF TRANSBLK DIS
(address
3212
) should be set to
YES
. This blocks also the distance protection if an external
fault was previously detected by the earth fault protection only.
Echo function
The echo function settings are common to all weak infeed measures and summarized in tabular form in Section
2.11.2.2.
Note
The
„ECHO SIGNAL“
(No. 4246) must be separately allocated to the output relay for the transmitter actuation
as it is not included in the transmit signals of the transmission functions.
2.9.8
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
3201
FCT Telep. E/F
ON
OFF
ON
Teleprotection for Earth Fault O/C
3202
Line Config.
Two Terminals
Three terminals
Two Terminals
Line Configuration
3203A
Send Prolong.
0.00 .. 30.00 sec
0.05 sec
Time for send signal prolongation
3207A
Delay for alarm
0.00 .. 30.00 sec
10.00 sec
Unblocking: Time Delay for Alarm
3208
Release Delay
0.000 .. 30.000 sec
0.000 sec
Time Delay for release after
pickup
3209A
TrBlk Wait Time
0.00 .. 30.00 sec;
∞
0.04 sec
Transient Block.: Duration exter-
nal flt.
3210A
TrBlk BlockTime
0.00 .. 30.00 sec
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
3212A
EF TRANSBLK DIS
YES
NO
YES
EF transient block by DIS
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...