Functions
2.7 Teleprotection for Distance Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
210
Figure 2-100
Reverse interlocking - functional principle and grading example
2.7.12
Transient Blocking
In the overreach schemes, the transient blocking provides additional security against erroneous signals due to
transients caused by clearance of an external fault or by fault direction reversal during clearance of a fault on
a parallel line.
The principle of transient blocking scheme is that following the incidence of an external fault, the formation of
a release signal is prevented for a certain (settable) time. In the case of permissive schemes, this is achieved
by blocking of the transmit and receive circuit.
Figure 2-101 shows the principle of the transient blocking for a permissive scheme.
If, following fault detection, a non-directional fault or a fault in the reverse direction is determined within the
waiting time
TrBlk Wait Time
(address
2109
), the transmit circuit and the release of the overreaching zone
Z1B are prevented. This blocking is maintained for the duration of the transient blocking time
TrBlk
BlockTime
(address
2110
) also after the reset of the blocking criterion. But if a trip command is already
present in Z1, the transient blocking time
TrBlk BlockTime
is terminated and thus the blocking of the signal
transmission scheme in the event of an internal fault is prevented.
In the case of the blocking scheme, the transient blocking also prolongs the received block signal as shown in
the logic diagram Figure 2-101. After expiration of
TrBlk BlockTime
(address
2110
) the delay time
Release Delay
(address
2108
) is restarted.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...