Functions
2.7 Teleprotection for Distance Protection (optional)
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
187
2.7
Teleprotection for Distance Protection (optional)
2.7.1
General
Purpose of Teleprotection
Faults which occur on the protected line, beyond the first distance zone, can only be cleared selectively by the
distance protection after a delay time. On line sections that are shorter than the smallest sensible distance set-
ting, faults can also not be selectively cleared instantaneously.
To achieve instantaneous and selective tripping on 100 % of the line length for all faults by the distance protec-
tion, the distance protection can exchange and process information with the opposite line end by means of tele-
protection schemes. This is realized by means of send and receive contacts.
As an alternative, digital communication lines can be used for signal transmission.
Teleprotection Schemes
A distinction is made between underreach and overreach schemes.
In underreach schemes, the protection is set with a normal grading characteristic. If a trip command occurs in
the first zone, the other line end receives this information via a transmission channel. There the received signal
initates a trip, either by activation of overreach zone Z1B or via a direct trip command.
7SD5 allows:
• PUTT (Pickup),
• Permissive Underreach Transfer Trip with Zone Acceleration Z1B (PUTT),
• Direct (Underreach) Transfer Trip
In overreach schemes, the protection works from the start with a fast overreaching zone. This zone, however,
can only cause a trip if the opposite end also detects a fault in the overreaching zone. A release (unblock) signal
or a block signal can be transmitted. The following teleprotection schemes are differentiated:
Permissive (release) schemes:
• Permissive Overreach Transfer Trip (POTT) with overreaching zone Z1B
• Directional comparison,
• Unblocking with overreaching zone Z1B.
Blocking scheme:
• Blocking of overreaching zone Z1B.
Schemes via pilot wire:
• Pilot Wire Comparison
• Reverse Interlocking
Since the distance zones function independently, an instantaneous trip in Z1 without a release or blocking
signal is always possible. If fast tripping in Z1 is not required (e.g. on very short lines), then Z1 must be delayed
with T1.
Содержание SIPROTEC
Страница 20: ...Contents SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 20 ...
Страница 351: ...Functions 2 18 Synchronism and Voltage Check optional SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 351 ...
Страница 494: ...Functions 2 27 Command Processing SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 494 ...
Страница 640: ...Technical Data 4 27 Dimensions SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 640 ...
Страница 657: ...Appendix A 2 Terminal Assignments SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 657 7SD5 W ...
Страница 754: ...Appendix A 10 Measured Values SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 754 ...
Страница 756: ...Literature SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 756 ...
Страница 768: ...Glossary SIPROTEC 7SD5 Manual C53000 G1176 C169 5 Release date 02 2011 768 ...