4.1 General Device Data
456
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Vibration and Shock Stress During Transport
4.1.7
Climatic Stress Tests
Temperatures
1
)
Humidity
Standards:
IEC 60255-21 and IEC 60068
Oscillation
IEC 60255-21-1, Class II;
IEC 60068-2-6
Sinusoidal
5 Hz to 8 Hz:
±
7.5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration
frequency sweep 1 octave/min
20 cycles in 3 orthogonal axes
Shock
IEC 60255-21-2, Class I;
IEC 60068-2-27
Semi-sinusoidal
15 g acceleration, duration 11 ms,
each 3 shocks (in both directions of the 3 axes)
Continuous Shock
IEC 60255-21-2, Class I;
IEC 60068-2-29
Semi-sinusoidal
10 g acceleration, duration 16 ms,
each 1000 shocks (in both directions of the 3
axes)
Standards:
IEC 60255-6
Type tested (acc. IEC 60086-2-1 and -2, Test
Bd, for 16 h)
–13
°
F to +185
°
F or -25.00
°
C to +85
°
C
Permissible temporary operating tempera-
ture (tested for 96 h)
– 4.00
°
F to +158
°
F or –20
°
C to +70
°
C (legibil-
ity of display may be restricted from +131
°
F or
+55
°
C)
Recommended for permanent operation (ac-
cording to IEC 60255-6)
+23
°
F to +131
°
F or -5
°
C to +55
°
C
Limiting Temperatures for Storage
–13
°
F to +131
°
F or -25
°
C to +55
°
C
Limiting temperatures for transport
–13
°
F to +158
°
F or -25
°
C to +70
°
C
STORE AND TRANSPORT THE DEVICE WITH FACTORY PACKAGING.
1
) UL–certified according to Standard 508 (Industrial Control Equipment):
Limiting temperatures for normal operation
(i.e. output relays not energized)
–4
°
F to +158
°
F or -20
°
C to +70
°
C
Limiting temperatures with maximum load
(max. cont. permissible energization of
inputs and outputs)
+23
°
F to +131
°
F or –5
°
C to +55
°
C for 7SJ62
+23
°
F to +104
°
F or –5
°
C to +40
°
C for
7SJ63/64
Permissible humidity
Mean value per year
≤
75 % relative humidity;
on 56 days of the year up to 93 % relative hu-
midity; condensation must be avoided!
Siemens recommends that all devices be installed such that they are not exposed to direct sun-
light, nor subject to large fluctuations in temperature that may cause condensation to occur.
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...