3 Parameterization
3.3 Parameterizing the IO Controller
75
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
3.3
Parameterizing the IO Controller
3.3.1
PROFINET IO Configuration
The SIPROTEC IO device is configured using the parameterization software of the IO controller. For this
purpose, the GSDML file of the SIPROTEC IO device is loaded into the parameterization software of the IO
controller. This file contains the description of the device properties and the configuration options of the
EN100-E+ and EN100-O+ with PROFINET IO.
The GSDML file is named GSDML-V2.25-Siemens-SIPROTEC-<date>.xml,
for example GSDML-V2.25-Siemens-SIPROTEC4-20120525.xml,
with <date> being the version date of the GSDML file.
The GSDML file can be downloaded, see Chapter 1.1 Extended Scope of Delivery.
If communication to an EN100-E+ (electrical) is launched with the configuration for an EN100-O+ (optical) or
vice versa, all submodules of the DAP are reported as being invalid and displayed accordingly in the device
diagnosis of the IO controller. Communication to the IO modules is possible in spite of this.
3.3.2
Siemens S7 PLC and Step7
Observe the following information concerning the configuration when using the SIPROTEC devices via
PROFINET IO in combination with Siemens S7 PLC and the Step 7 parameterization software.
Find more information on Siemens S7 PLC and the Step7 parameterization software at:
http://support.automation.siemens.com
The following book provides, among others, more detailed information on the integration of the blocks and func-
tions relevant for PROFINET IO into an S7 program:
Pigan, R.; Metter, M.
Automating with PROFINET
Industrial Communication based on Industrial Ethernet
Publishing House: Publics Corporate Publishing Erlangen
ISBN: 978-3-89578-294-7
3.3.2.1 PLC in STOP during Communication with the SIPROTEC Device
If the PLC is switched from RUN to STOP or switches to STOP due to an internal PLC program response during
PROFINET IO communication with the SIPROTEC device, the running PROFINET IO communication between
the IO controller of the PLC and the IO device of the SIPROTEC device remains active. Cyclic data exchange
continues, that is, communication is not interrupted.
For all IO modules in output direction, however, the IOPS from the PLC are set to "bad" and the data of these
IO modules are transmitted with all values equaling zero.
When changing from RUN to STOP, the status of the outputs in the SIPROTEC device remains in the status
during RUN.
The tagging SysIntErr. in the SIPROTEC device (see Chapter 2.10) is not set.
NOTE
Observe the information in Chapter 2.13 for setting the minimum PROFINET IO cycle time of the
SIPROTEC-IO device if IEC 61850 and GOOSE are used simultaneously.