Technical Data
Load Capability of the Voltage Divider
Terminals 1B – 4B
Max. permissible continuous voltage
55 V AC
Continuous output power 2 W
Max. permissible voltage (60 s)
550 V AC
Max. dissipated power
185 W (max. 60 s, recovery time 600 s)
i
i
NOTE
The minimum load of 200 kΩ (protection relay input impedance) is needed to reach the necessary accu-
racy.
Weight
The weight of the device is 1.9 kg (4.2 lb.).