3.1 Mounting And Connections
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
74
It is possible to convert the R485 interface to a RS232 interface by changing the jumper positions and vice-
versa.
The jumper positions for the alternatives RS232 or RS485 (as in Figure 3-10) are derived from the following
Table.
Table 3-16
Configuration for RS232 or RS485 on the interface module
The jumpers X5 to X10 must be plugged in the same way!
The jumpers are preset at the factory according to the configuration ordered.
3.1.2.5
Reassembly
The device is assembled in the following steps:
• Insert the boards carefully in the housing. The mounting locations are shown in Figures 3-2.
• Plug in the plug connectors of the ribbon cable onto the input/output modules I/O and then onto the
processor module C-CPU-2. Be careful not to bend any connector pins! Do not apply force!
• Connect the plug connectors of the ribbon cable between the C-CPU-2 board and the front panel to the front
panel plug connector.
• Press the plug connector interlocks together.
• Replace the front panel and screw it tightly to the housing
• Replace the covers again.
• Screw the interfaces on the rear panel of the device tight again.
This activity does not apply if the device is for surface mounting.
3.1.3
Mounting
3.1.3.1
Panel Flush Mounting
For the 1/1 housing size (Figure 3-14) there are six covers and six holes.
• Remove the 4 covers at the corners of the front cover, for size 1/1 the two covers located centrally at the top
and bottom also have to be removed. The 6 elongated holes in the mounting bracket are revealed and can
be accessed.
• Insert the device into the panel cut-out and fasten it with four or six screws. For dimensions refer to Appendix
A.4
• Mount the six covers.
• Connect the ground on the rear plate of the device to the protective ground of the panel. Using at least one
M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other
control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm
2
.
Jumper
X5
X6
X7
X8
X10
X11
X12
X13
RS232
1-2
1-2
1-2
1-2
1-2
2-3
1-2
1-2
RS485
2-3
2-3
2-3
2-3
2-3
2-3
1-2
1-2
Содержание SIPROTEC 7VU681
Страница 8: ...Preface SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 8 ...
Страница 12: ...Contents SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 12 ...
Страница 100: ...Literature SIPROTEC 7VU683 User Manual C53000 G1176 C368 1 Release Date 07 2012 100 ...
Страница 110: ...Appendix A 4 Dimension SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 110 ...
Страница 112: ...Index SIPROTEC 7VU681 User Manual C53000 G1176 C368 1 Release Date 07 2012 112 ...