Function
2.2 Protection
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
50
2.2.2
Zero Sequence Overcurrent Protection
This device supplies 2 stages of definite time zero sequence overcurrent protection.
Figure 2-26
Logic Diagram of the Zero Sequence Overcurrent Protection
1. Zero sequence voltage function can be enabled or disabled by setting the parameter
9011 3U0 Control
to
YES
or
NO
.
2.PT broken wire cannot block zero sequence overcurrent protection.
3.After the trip signal is released, the dropout of the voltage signal cannot reset the trip signal, only current
dropout can reset the trip signal.