2 Functions
38
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-1
Transformer bank, consisting of 3 single-phase auto-transformers with current
comparison via each single phase
• Such current comparison is more sensitive to 1-phase earth faults in one of the
transformers than the normal differential protection. This has a certain importance
considering that 1-phase earth faults are the most probable faults in such banks.
• On the other hand, the compensation winding cannot and must not be included into
this protection even if it is accessible and equipped with current transformers. This
application variant is based on the current law in that all currents flowing into a
winding must total to zero.
• If this protection variant is desired, set address 105 to
PROT. OBJECT
=
Autotr.
node
.
• Equal setting is valid for generators and motors. The setting
PROT. OBJECT
=
Generator/Motor
also applies to series reactors and shunt reactors, if a com-
plete 3-phase set of current transformers is connected to both sides.
• For the operation of mini-busbars set
PROT. OBJECT
=
3ph Busbar
. The
maximum number of feeders is determined by the number of three-phase measure-
ment inputs of the device. 7UT613 and 7UT633 allow a maximum number of 3,
7UT635 a maximum of 5 measuring locations. This setting applies also to short
lines which are terminated by two sets of current transformers. „Short “ means that
the current transformer connections from the CTs to the device cause no impermis-
sible burden for the current transformers.
• If the device is used as busbar as 1-phase device or via summation transformer as
3-phase device, the setting
PROT. OBJECT
=
1ph Busbar
applies. The maximum
number of feeders is determined by the number of single-phase measurement
inputs of the device (7UT613 and 7UT633 provide up to 9, 7UT635 up to 12 mea-
surement inputs).
Differential Protec-
tion
The differential protection is the main protective function of the device. Address
112
DIFF. PROT.
is thus set to
Enabled
.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...