2.22 Additional Functions
315
7UT613/63x Manual
C53000-G1176-C160-2
2.22.6.2 Information List
2.22.7 Flexible Function
The flexible functions can be used for various protection, supervision and measuring
purposes. Up to 12 flexible functions can be created in 7UT613/63x.
The flexible functions can be configured as independent protective functions (e.g.
further time overcurrent protection for measuring locations), create additional stages
for already existing protective functions or used for monitoring or control functions.
When determining the function scope (Section 2.1.3) the number of flexible functions
can be given.
Every flexible function is configured by defining analogue input value(s), type of mea-
sured value processing and logic link. Setting limit values, delay times, etc. can be
reset with the setting groups (see section 2.1.5 under „Setting Groups“)
2.22.7.1 Function Description
General
When creating a flexible function you determine how the measured values (lead to the
device) are to be processed. The measured values can be directly detected (e.g. cur-
rents) or mathematically combined (e.g. positive sequence system of the currents or
current and voltage power).
The measured values can be monitored for overshooting or undershooting of a con-
figurable threshold value. Delays, blocking and logical configuration possibilities are
possible via user-definable logic functions (CFC).
A flexible function can signal the state that needs to be monitored, be used as control
function or initiate tripping of one or more circuit breakers. The latter starts the circuit
breaker failure protection with the trip command, if it has the same assignment char-
acteristics.
Measured Values
All measured values given to the device can be used as analogue input quantities for
a flexible function.
Three-phase values can be processed together or individually. Together means that
the three-phase currents of a measuring point exceeding a common limit value have
to be monitored, but have to be announced and processed individually. All settings are
for all three currents. A flexible function can be created for each of the three phase
No.
Information
Type of In-
formation
Comments
-
Meter res
IntSP_Ev
Reset meter
888
Wp(puls)=
PMV
Pulsed Energy Wp (active)
889
Wq(puls)=
PMV
Pulsed Energy Wq (reactive)
916
Wp
∆
=
-
Increment of active energy
917
Wq
∆
=
-
Increment of reactive energy
924
Wp+=
MVMV
Wp Forward
925
Wq+=
MVMV
Wq Forward
928
Wp-=
MVMV
Wp Reverse
929
Wq-=
MVMV
Wq Reverse
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...