1 Introduction
24
7UT613/63x Manual
C53000-G1176-C160-2
Busbar Protection
• 1-phase differential protection for a busbar with up to 9 or 12 feeders (depending
on the version)
• Either one relay per phase or one relay connected via interposed summation
current transformers
• Tripping characteristic with current restraint
• Short tripping time
• Insensitivity to DC components and current transformer saturation
• High level of stability even with different degrees of current transformer saturation
• Monitoring of the current connections with operation currents.
Earth Fault Differ-
ential Protection
• Earth fault protection for earthed transformer windings, generators, motors, shunt
reactors, or starpoint formers
• Short command duration
• High sensitivity for earth faults within the protected zone
• High stability against external earth faults using the magnitude and phase relation-
ship of through-flowing earth current.
• 2 earth-fault differential protection functions possible
High-impedance
Unit Protection
• Highly sensitive fault current detection using a common (external) burden resistor
• Short tripping time
• Insensitive against DC components and current transformer saturation
• High stability with optimum matching
• Suitable for earth fault detection on earthed generators, motors, shunt reactors, and
transformers, including auto-transformers, with or without earthed starpoint.
• Suitable for any voltage measurement (via the resistor current) for application of
high-impedance unit protection
Tank Leakage Pro-
tection
• For transformers or reactors the tank of which is installed isolated or with high re-
sistance
• Monitoring of the current flowing between the tank and ground
• Can be connected via a „normal“ current input of the device or the special highly
sensitive current input (3 mA smallest setting).
Time Overcurrent
Protection for
Phase Currents and
Residual Current
• Two definite time delayed overcurrent stages for each of the phase currents and the
residual (threefold zero sequence) current, can be assigned to any of the sides of
the protected object or to any measuring point
• Additionally, one inverse time delayed overcurrent stage for each of the phase cur-
rents and the residual current
• Selection of various inverse time characteristics of different standards is possible,
alternatively a user defined characteristic can be specified
• The stages can be combined as desired, different characteristics can be selected
for phase currents on the one hand and the residual current on the other
• External blocking facility for any stage (e.g. for reverse interlocking)
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...