2 Functions
186
7UT613/63x Manual
C53000-G1176-C160-2
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has already been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times of the
setting value is present.
Using the overcurrent stage
IEp
(address
2421
) earth faults can also be detected with
weak fault currents. Since the starpoint current originates from one single current
transformer, it is not affected by summation effects evoked by different current trans-
former errors like, for example, the zero sequence current derived from phase cur-
rents. Therefore, this address can be set to very sensitive. Consider that the inrush
restraint function cannot operate below 10 % nominal current (lower limit of harmonic
filtering). An adequate time delay could be reasonable for very sensitive setting if
inrush restraint is used.
Since this stage also picks up with earth faults in the network, the time multiplier (ad-
dress
2422
T IEp
) has to be coordinated with the grading coordination chart of the
network for earth faults. In most cases, shorter tripping times than for phase currents
may be set since a galvanic separation of the zero sequence systems of the connect-
ed power system sections is ensured by a transformer with separate windings.
The time multiplication factor may also be set to
∞
. If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the
IEp
–stage is not
required, select address
124
DMT/IDMT Earth
=
Definite Time
when configuring
the protection functions.
If under address
2424
TOC DROP-OUT
the
Disk Emulation
are set, dropout is pro-
duced in accordance with the dropout characteristic, as set out in the functional de-
scription of the inverse time overcurrent protection under margin heading „Dropout Be-
haviour“.
Overcurrent Stage
I
Ep
with ANSI Char-
acteristics
The inverse time stage, depending on the configuration, enables the user to select dif-
ferent characteristics. With the ANSI characteristics (address
124
DMT/IDMT Earth
=
TOC ANSI
) the following is made available in address
2426
ANSI CURVE
:
•
Definite Inv.
,
•
Extremely Inv.
,
•
Inverse
,
•
Long Inverse
,
•
Moderately Inv.
,
•
Short Inverse
, and
•
Very Inverse
.
The characteristics and equations they are based on are listed in the „Technical Data“.
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has already been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times the
setting value is present.
Using the time overcurrent stage
IEp
(address
2421
) earth faults can also be detect-
ed with weak fault currents. Since the starpoint current originates from one single
current transformer, it is not affected by summation effects evoked by different current
transformer errors like, for example, the zero sequence current derived from phase
currents. Therefore, this address can be set to very sensitive. Consider that the inrush
restraint function cannot operate below 10 % nominal current (lower limit of harmonic
filtering). An adequate time delay could be reasonable for very sensitive setting if
inrush restraint is used.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...