2 Functions
148
7UT613/63x Manual
C53000-G1176-C160-2
Note
When delivered from factory, the restricted earth fault protection is switched OFF. The
reason is that the protection must not be in operation unless at least the assigned side
and CT polarity have been properly set before. Without proper settings, the device
may show unexpected reactions (incl. tripping)!
The sensitivity of the protection is determined by
I-REF>
setting (address
1311
). This
is the earth fault current which flows through the starpoint lead of the protected object
(transformer, generator, motor, shunt reactor). A further earth current which may be
supplied from the network does not influence the sensitivity. The setting value refers
to the rated current of the protected side of the main protected object or, in case of a
further protected object, to the rated operation current of the corresponding measuring
location.
Note
In case of large mismatching, the indication 199.2494
(EarthDiff.Fault: MatchFac I-CT. too lar/sml.) appears. The setting value should then
be increased.
The set value can be increased in the tripping quadrant depending on the arithmetic
sum of the currents (restraint by the sum of all current magnitudes) which is set at ad-
dress
1313
SLOPE
. This parameter can only be set with DIGSI at
Additional Settings
.
The preset value 0 is normally adequate.
In special cases it may be advantageous to delay the trip signal of the protection. This
can be done by setting an additional delay time (address
1312
T I-REF>
). This pa-
rameter can only be set with DIGSI at
Additional Settings
. This additional time delay
is usually set to 0. This setting is a pure additional delay time which does not include
the inherent operating time of the protection.
Additional Restrict-
ed Earth Fault Pro-
tection Functions
In the aforementioned description, the first restricted earth fault protection is described
respectively. The differences in the parameter addresses and message numbers of
the first and second restricted earth fault protection are illustrated in the following
table. The positions marked by x are identical.
Note
In the following parameter overview the current values
I
/
I
NS
refer to the rated current
of the side to be protected of the main protected object. If the restricted earth fault pro-
tection is not referred to the main protected object, the rated current of the 3-phase
measuring location is the applicable reference value.
Parameter addresses
Message no.
1. Restricted earth fault protection
13xx
199.xxxx(.01)
2. Restricted earth fault protection
14xx
205.xxxx(.01)
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...