2 Functions
134
7UT613/63x Manual
C53000-G1176-C160-2
mentioned address. The restraint with harmonics does not influence the stage
I-
DIFF>>
.
The inrush restraint can be extended by the so-called "crossblock" function. This
means that on harmonic content overshoot in only one phase all three phases of the
differential stage I
DIFF>
stage are blocked. The duration for which the crossblock func-
tion is active can be limited at address
1272
CROSSB. 2. HARM
. Setting is in multiple
of the AC-cycle. This parameter can only be set with DIGSI at
Additional Settings
. If
set to
0
(pre-setting is
3
) the protection can trip when the transformer is switched on
a single-phase fault even while the other phases carry inrush current. If set to
∞
the
crossblock function remains effective for as long as high-order harmonics are detected
in any phase.
Apart from the second harmonic, the 7UT613/63x can provide restraint with a further
harmonic. Address
1207
RESTR. n.HARM.
is used to disable this harmonics re-
straint, or to select the harmonic for it. Available for selection are the
3. Harmonic
and the
5. Harmonic
.
Steady-state overexcitation of transformers is characterised by odd harmonic content.
The 3rd or 5th harmonic is suitable to detect overexcitation. As the third harmonic is
often eliminated in transformers (e.g. in a delta winding), the fifth harmonic is more
commonly used.
Converter transformers also produce odd harmonics which are practically absent in
the case of an internal short-circuit.
The harmonic content intended for blocking the differential protection is set at address
1276
n. HARMONIC
. For example, if the 5th harmonic restraint is used to avoid trip
during overexcitation, 30 % (default setting) are convenient.
Harmonic restraint with the n-th harmonic operates individually per phase. However,
it is also possible – as it is for the inrush restraint – to set the protection in such manner
that not only the phase with harmonic content overshoot but also the other phases of
the differential stage
I-DIFF>
are blocked (so-called "crossblock" function). The du-
ration for which the crossblock function is active can be limited at address
1277
CROSSB. n.HARM
. Setting is in multiple of the AC-cycle. This parameter can only be
set with DIGSI at
Additional Settings
. If set to
0
the crossblock function remains ef-
fective for as long as high-order harmonics are detected in any phase. When set to
∞
,
the crossblock function is always active. .
If the differential current exceeds the magnitude set at address
1278
IDIFFmax
n.HM
no n-th harmonic restraint takes place. This parameter can only be altered in
DIGSI at
Display Additional Settings
.
Note
The current values
I
/
I
NO
in the settings overview below always refer to the rated
current of the main protected object. The current values
I
/
I
NS
always refer to the rated
current of the relevant side of the main protected object.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...