2.2 Differential Protection
131
7UT613/63x Manual
C53000-G1176-C160-2
Differential Current
Monitoring
With busbar protection or short-line protection differential current can be monitored.
At address
1208
I-DIFF> MON.
the monitoring can be set to
ON
and
OFF
. Its use is
only sensible if one can distinguish clearly between operational error currents caused
by missing transformer currents and fault currents caused by a fault in the protected
object.
The pickup value
I-DIFF> MON.
(address
1281
) must be high enough to avoid a
pickup caused by a transformation error of the current transformers and by minimum
mismatching of different current transformers. On the other hand, the pickup value
must lie clearly below the differential protection (
I-DIFF>
, address
1221
); otherwise
no differentiation between operational errors caused by missing secondary currents
and fault currents due to short-circuit in the protected object would be possible. The
pickup value is referred to the rated current of the protected object. Time delay
T I-DIFF> MON.
(address
1282
) applies to the annunciation and blocking of the
differential protection. This setting ensures that blocking with the presence of faults
(even of external ones) is avoided. The time delay usually amounts to a few seconds.
Feeder Current
Guard
With busbars and short lines a release of the trip command can be set if one of the
incoming currents is exceeded. The differential protection only trips if one of the mea-
sured currents exceeds the threshold
I> CURR. GUARD
(address
1210
). The pickup
value is referred to the rated current of the respective side. With setting 0.00 I/InS (pre-
setting) this release criterion will not be used.
If the feeder current guard is set (i. e. to a value of > 0), the differential protection will
not trip before the release criterion is given. This is also the case if, in conjunction with
very high differential currents, the extremely fast instantaneous value scheme has de-
tected the fault already after a few milliseconds.
Trip Characteristic
Differential Current
The parameters of the tripping characteristic are set in addresses
1221
to
1265
.
Figure 2-49 illustrates the meaning of the different settings. The numbers at the differ-
ent branches of the characteristic signify the addresses of the settings.
I-DIFF>
(address
1221
) is the pickup value of the differential current. This is the total
fault current into the protected object, regardless of the way this is distributed between
the sides. The pickup value is referred to the rated current of the protected object. You
may select a high sensitivity (small pickup value) for transformers (presetting
0.2 ·
I
N Obj
). With reactors, generators and motors the sensitivity can be set even
higher, provided that the current transformer sets are of similar design. A higher value
(above rated current) should be selected for lines and busbars. Higher measuring tol-
erances must be expected if the rated currents of the current transformers differ ex-
tensively from the rated current of the protected object, or if there are multiple measur-
ing locations.
In case of busbars and short lines, the through-flowing current can increase substan-
tially, depending on the system. The unstable
I-DIFF>>
stage could trip. In such
cases
I-DIFF>>
should be set to
∞
.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...