2.14 Impedance Protection (ANSI 21)
95
7UM61 Manual
C53000-G1176-C127-3
covers the network. It should be noted that high voltage side 1-pole faults cause im-
pedance measurement errors due to the star-delta connection of the unit transformer
on the lower voltage side. An unwanted operation of the stage can be excluded since
the fault impedances of power system faults are modeled too high.
Faults outside this range are switched off by the
T END
final time stage.
Depending on the switching status of the system, it may be useful to extend the
ZONE
Z1
,
T-Z1
undelayed tripping zone. If, for example, the high-voltage side circuit
breaker is open, the pickup can only be caused by a fault in the power unit. If consid-
eration of the circuit breaker auxiliary contact is possible, a so-called overreach zone
ZONE Z1B
can be made effective (see also Section 2.14.2, Grading of the Machine
Impedance Protection figure).
Figure 2-28
Tripping Characteristics of the Impedance Protection
Tripping Logic
The
T END
time delay is started subsequent to the protection pickup, establishing the
the fault loop. The loop impedance components are compared with the limit values of
the zones previously set. The tripping is executed if the impedance is within its zone
during the the course of the corresponding time stage.
For the first Z1 zone and also for the Z1B overreach zone, the time delay will in most
cases be zero or at least very short. i.e. tripping occurs as soon as it is established that
the fault is within this zone.
The Z1B overreach stage can be enabled from outside, via a binary input.
For the Z2 zone which may extend into the network, a time delay is selected over-
reaching the first stage of the power system protection.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...