2.11 Underexcitation (Loss-of-Field) Protection (ANSI 40)
83
7UM61 Manual
C53000-G1176-C127-3
Delay Times
If the static limit curve consisting of the characteristics 1 and 2 is exceeded, the voltage
regulator must first have the opportunity of increasing the excitation. For this reason,
a warning message due to this criterion is ”long-time" delayed (at least 10 s for
3004
T CHAR. 1
and
3007
T CHAR. 2
).
However if an external excitation monitoring signals the failure of an excitation voltage
to the device via a binary input, a switch-off can be performed with a short time delay.
Table 2-4
Setting the Underexcitation Protection
Note:
If very short time delays are selected, dynamic balancing procedures may
cause unwanted operations. For this reason, it is recommended to set time values of
0.05 s or higher.
2.11.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Characteristic 1 and 2 static stability undelayed
Annunciation:
Exc < Anr
Characteristic 1 and 2 static stability long-time delayed
T CHAR. 1 = T CHAR. 2
≈
10 s
Trippings
Err<1 TRIP / Err<2 TRIP
Characteristic 1 and 2 Excitation
Voltage Failure
short–time delayed
T SHRT Uex<
≈
1.5 s
Tripping
Err< UPU < TRIP
Characteristic 3 dynamic stability
short–time delayed
T CHAR 3
≈
0.5 s
Tripping
Exc<3 TRIP
Addr.
Parameter
Setting Options
Default Setting
Comments
3001
UNDEREXCIT.
OFF
ON
Block relay
OFF
Underexcitation Protection
3002
1/xd CHAR. 1
0.25 .. 3.00
0.41
Conductance Intersect Character-
istic 1
3003
ANGLE 1
50 .. 120
°
80
°
Inclination Angle of Characteristic
1
3004
T CHAR. 1
0.00 .. 60.00 sec;
∞
10.00 sec
Characteristic 1 Time Delay
3005
1/xd CHAR. 2
0.25 .. 3.00
0.36
Conductance Intersect Character-
istic 2
3006
ANGLE 2
50 .. 120
°
90
°
Inclination Angle of Characteristic
2
3007
T CHAR. 2
0.00 .. 60.00 sec;
∞
10.00 sec
Characteristic 2 Time Delay
3008
1/xd CHAR. 3
0.25 .. 3.00
1.10
Conductance Intersect Character-
istic 3
3009
ANGLE 3
50 .. 120
°
90
°
Inclination Angle of Characteristic
3
3010
T CHAR 3
0.00 .. 60.00 sec;
∞
0.30 sec
Characteristic 3 Time Delay
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...