4.19 Motor Starting Time Supervision (ANSI 48)
333
7UM61 Manual
C53000-G1176-C127-3
4.19 Motor Starting Time Supervision (ANSI 48)
Setting Ranges / Increments
Tripping Characteristic
Dropout Ratio
Tolerances
Influencing Variables for Pickup Values
Motor Startup Current
I
STARTUP
for
I
N
= 1 A
0.10 A to 16.00 A
Increments 0.01 A
for
I
N
= 5 A
0.50 A to 80.00 A
Increments 0.05 A
Pickup Threshold for Startup
Detection
I
STRT DETECT.
for
I
N
= 1 A
0.60 A to 10.0 A
Increments 0.01 A
for
I
N
= 5 A
3.00 A to 50.00 A
Increments 0.05 A
Maximum Startup Time
T
Max. STARTUP
1.0 s to 180.0 s
Increments 0.1 s
Admissible Locked Rotor Time
T
LOCKED-ROTOR
0.05 s to 120.0 s or
∞
(in-
effective)
Increments 0.1 s
I
rms
/
I
STARTUP DETECT.
approx. 0.95
Pickup Threshold
for
I
N
= 1 A
1 % of setting value or 10 mA
for
I
N
= 5 A
1 % of setting value or 50 mA
Time Delay
5 % or 30 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...