4.12 Frequency Protection (ANSI 81)
325
7UM61 Manual
C53000-G1176-C127-3
4.12 Frequency Protection (ANSI 81)
Setting Ranges / Increments
Times
Dropout Difference
Dropout Ratio
Tolerances
Influencing Variables
Number of Frequency Elements
4; can be set to f> or f<
Pickup Frequency f> or f<
40 Hz to 65.00 Hz
Increments 0.01 Hz
Delay Times
T f1
T f2 to T f4
0.00 s to 600.00 s
0.00 s to 100.00 s
Increments 0.01 s
Increments 0.01 s
Undervoltage Blocking
(Positive Sequence Component U
1
)
10.0 V to 125.0 V and 0 V
(no blocking)
Increments 0.1V
The set times are pure delay times.
Pickup Times f>, f<
Dropout Times f>, f<
approx. 100 ms
approx. 100 ms
f = I Pickup Value – Dropout Value I
approx. 20 mHz
Dropout Ratio for Undervoltage Blocking
approx. 1.05
Frequencies f>, f<
Undervoltage Blocking
Time Delays T(f<, f<)
10 mHz (at U = U
N
, f = f
N
)
1 % of setting value or 0.5 V
1 % of setting value or 10 ms
Power Supply DC Voltage in Range
0.8
≤
U
PS
/U
PSN
≤
1.15
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
0.5 %/10 K
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
1 %
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...