2 Functions
206
7UM61 Manual
C53000-G1176-C127-3
2.34.4 Statistics
Tripping commands from the device are counted. Currents of the last disconnections
instigated by the device are logged. Disconnected fault currents are accumulated for
each breaker pole.
2.34.4.1 Functional Description
Number of Trips
The number of trips initiated by the 7UM61 is counted, as long as the position of the
circuit breaker is monitored via binary inputs. Hereby it is necessary that the internal
pulse counter is allocated in the matrix to a binary input that is controlled by the circuit
breaker OPEN position. The pulse metered value can be found in the "
Statistics
"
group if the option "Measured and Metered Values Only" was enabled in the configu-
ration matrix.
Switch-Off Values
(at Trip)
Additionally the following switch-off values appear in the fault indications for each trip
signal:
• the primary currents in all three phases in kA
• the three phase-earth-voltages in kV
• primary active power P in kW, MW or GW (precisely averaged power)
• primary reactive power Q in kVA, MVA or GVA (precisely averaged power)
• Frequency in Hz
Operating Hours
The accumulated operating hours under load are also stored (= current value in at
least one phase is greater than the limit value
281
set under address
BkrClosed I
MIN
).
Accumulated Shut-
down Currents
The shutdown currents for each phase indicated at every trip command individually
are accumulated and stored.
The counter and memory levels are secured against loss of auxiliary voltage.
Setting / Resetting
Setting or resetting of these statistical counters takes place under the menu item
AN-
NUNCIATION
→
STATISTICS
by overwriting the counter values displayed.
Startup Behaviour
Start
Startup occurs after each switching on of the supply voltage.
Initial Start
Initial start occurs after initialization of the device by DIGSI
®
4
Restart
Restart occurs after loading a parameter set or after reset
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...