2.31 External Trip Functions
189
7UM61 Manual
C53000-G1176-C127-3
2.31 External Trip Functions
Any signals from external protection or supervision units can be incorporated into the
processing of the digital machine protection 7UM61 via binary inputs. Like the internal
signals, they can be signaled, time delayed, transmitted to the trip matrix, and also in-
dividually blocked. By this means it is possible to include mechanical protection equip-
ment, e.g. Buchholz protection, into the processing of indications and trip commands
of the digital protection device. Furthermore interaction between protection functions
of different numerical machine protection devices of the 7UM6 series is possible.
2.31.1 Functional Description
Mode of Operation
The logic status of the corresponding assigned binary inputs is checked at cyclic inter-
vals. Change of input status is considered only if at least two consecutive status
checks have the same result. An additional time delay
8602
T DELAY
is available for
the trip command.
The following figure shows the logic diagram for direct input trippings. This logic is im-
plemented in all four times in the same manner, the function numbers of the indications
are each specified for the first external trip command channel.
Figure 2-74
Logic Diagram of Direct Input Trippings
2.31.2 Setting Notes
General
External trip command via binary inputs is only effective and available if configured at
addresses
186
EXT. TRIP 1
to
189
EXT. TRIP 4
as
Enabled
.
Disabled
is set
if the functions are not required. Addresses
8601
EXTERN TRIP 1
to
8901
EXTERN
TRIP 4
are used to switch the functions individually
ON
or
OFF
, or to block only the
trip command (
Block relay
).
Like the internal signals, they can be indicated as external trippings, time delayed and
transmitted to the trip matrix. The delay times are set at addresses
8602
T DELAY
through
8902
T DELAY
. Like for the protective functions, the dropout of the direct
input trippings is extended by the parametrized minimum duration
TMin TRIP CMD
.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...