2.15 Undervoltage Protection (ANSI 27)
105
7UM61 Manual
C53000-G1176-C127-3
2.15.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.15.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
4001
UNDERVOLTAGE
OFF
ON
Block relay
OFF
Undervoltage Protection
4002
U<
10.0 .. 125.0 V
75.0 V
U< Pickup
4003
T U<
0.00 .. 60.00 sec;
∞
3.00 sec
T U< Time Delay
4004
U<<
10.0 .. 125.0 V
65.0 V
U<< Pickup
4005
T U<<
0.00 .. 60.00 sec;
∞
0.50 sec
T U<< Time Delay
4006A
DOUT RATIO
1.01 .. 1.20
1.05
U<, U<< Drop Out Ratio
No.
Information
Type of In-
formation
Comments
6503
>BLOCK U/V
EM
>BLOCK undervoltage protection
6506
>BLOCK U<
EM
>BLOCK undervoltage protection U<
6508
>BLOCK U<<
EM
>BLOCK undervoltage protection U<<
6530
Undervolt. OFF
AM
Undervoltage protection switched OFF
6531
Undervolt. BLK
AM
Undervoltage protection is BLOCKED
6532
Undervolt. ACT
AM
Undervoltage protection is ACTIVE
6533
U< picked up
AM
Undervoltage U< picked up
6537
U<< picked up
AM
Undervoltage U<< picked up
6539
U< TRIP
AM
Undervoltage U< TRIP
6540
U<< TRIP
AM
Undervoltage U<< TRIP
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...