2 Functions
30
7ST6 Manual
E50417-G1176-C251-A3
2.1.2
Device
The device requires some general information. This may be, for example, the type of
indication to be issued in the event a power system fault occurs.
2.1.2.1
Trip Dependent Indications
The recording of indications masked to local LEDs, and the maintenance of spontane-
ous indications, can be made dependent on whether the device has issued a trip
signal. This information is then not output if during a system disturbance one or more
protection functions have picked up, but no tripping by the 7ST6 resulted because the
fault was cleared by a different device (e.g. on another line). These indications are
then limited to faults in the line to be protected.
The figure below illustrates the creation of the reset command for stored indications.
When the relay drops out, stationary conditions (fault display Target on PU / Target on
TRIP; Trip / No Trip) decide whether the new fault will be stored or reset.
Figure 2-1
Creation of the reset command for the memory of LED and LCD displays
2.1.2.2
Spontaneous Indications on the Display
You can determine whether or not the most important data of a fault event is displayed
automatically after the fault has occurred (see also „Fault indications“ in Section 2.19.1
„Auxiliary Functions“).
2.1.2.3
Setting Notes
Fault Indications
Pickup of a new protective function generally turns off any previously lit LEDs, so that
only the latest fault is displayed at any time. It can be selected whether the stored LED
displays and the spontaneous indications on the display appear upon renewed pickup,
or only after a renewed trip signal is issued. In order to enter the desired type of dis-
play, select the submenu Device in the SETTINGS menu. At address
610
FltDisp.LED/LCD
the two alternatives
Target on PU
and
Target on TRIP
(„No
trip - no flag“) are offered.
For devices with graphical display use parameter
615
Spont. FltDisp.
to specify
whether or not a spontaneous indication will appear automatically on the display (
YES
)
or not (
NO
). For devices with text display such indications will appear after a system
fault by any means.
You can set at address
620
T Backlight on
how long the display backlight will
remain on after an entry on the integrated keypad.
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7ST6
Страница 14: ...Contents 14 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 24: ...1 Introduction 24 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 254: ...3 Mounting and Commissioning 254 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 288: ...4 Technical Data 288 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 340: ...A Appendix 340 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 342: ...Literature 342 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 354: ...Index 354 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 355: ...Index 355 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 356: ...Index 356 7ST6 Manual E50417 G1176 C251 A3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...