
Configuration
60
7SS52 V4 Manual
C53000-G1176-C182-3
4.3.7
Normalized Current
Normally, the configuration tool determines the so-called normalized current
automatically by searching for the current transformer with the highest primary
nominal current when you exit the configuration. All parameters with the dimension l/
lno refer to this reference value. You can select any other normalized current in the
configuration tool under
Tools
→
Set Reference Value
. When exiting the
configuration you can choose between the calculated value or the one you have
defined in the dialog
Specifying a reference Value
(Figure 4-13, page 60). A lower
value allows you for example to increase the sensitivity of the differential current
supervision because it has a lower setting limit of 5% l/lno.
The normalized current which you define here may not exceed 5 times the value of the
configured maximum rated transformer current.
Figure 4-13 Select Reference Value
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...