Control During Operation
238
7SS52 V4 Manual
C53000-G1176-C182-3
6.3.5.2
Reset Blocking of Isolator Fault
Depending on the setting of the parameter
(
), there are dif-
ferent options of how the blocking will behave (Chapter 5.5.1.9, page 146).
The function is acknowledged by applying “
“ or via binary input
“ (
BI-FNo. 7/CU
) in the central unit.
from the PC
with DIGSI
To reset the blocking of the isolator fault at the
central unit
(PC linked to central unit)
proceed as follows:
Click
Control
in the navigation window.(see Figure 6-24, page 237).
Double-click
Reset blocking of isolator fault
in the function selection. The reset-
ting of the blocking can be protected by the password for the parameter set. If you
have activated this password you will be prompted to enter it before the command
is first executed since a connection was established. A dialog box opens for this
purpose.
Enter the correct password in the box named
Password
and then click
OK
. If the
password is wrong, you will receive an error message. When the password is cor-
rect, the blocking will be reset.
6.3.6
Trigger Initial Start and Restart
In case of an
initial start
will be cleared
- fault records
- fault annuciation buffer
- operational event buffer
- alarm list buffer
The device settings are contained in the parameter set and these are not changed in
case of an initial start.
The
restart,
to the contrary, is equivalent to switching 7SS52 V4 off and on. In case of
a
restart
operational annunciations, fault events, fault records, and the setting are
retained. Annunciations that are subject to general interrogation are retrieved and the
connection to the bay units is re-established.
Note
If the parameter
CU
) is set to
, the function
Reset blocking of isolator fault
is not available.
Caution!
Executing the commands
Reset
or
Resume
will clear all device buffers and Oscillo-
graphic Records. Before initial start you may want to back-up the settings and buffer
contents by means of the DIGSI Device Configuration.
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...