![Siemens SIPROTEC 7SS522 V4.6 Скачать руководство пользователя страница 199](http://html.mh-extra.com/html/siemens/siprotec-7ss522-v4-6/siprotec-7ss522-v4-6_manual_382521199.webp)
Fault Recording in the Bay Unit (”Local Fault Recording”)
183
7SS52 V4 Manual
C53000-G1176-C182-3
T-PRE
The parameter
T-PRE
(
7411/BU
)
is used to set the pre-trigger time for starting the
fault recording. The pre-trigger time starts at the specified time before the storage cri-
terion for fault record storage is fulfilled. The storage criterion is selected with the pa-
rameter
INITIATION
(
7402/BU
).
T-POST
The parameter
T-POST
(
7412/BU
)
is used to set the post-fault time for stopping the
fault recording. The post-fault time begins as soon as the stop criterion
for fault record
storage is fulfilled.
T-BINARY IN
The parameter
T-BINARY IN
(
7431/BU
)
is used to set the storage time when fault
recording is initiated via a binary input. The total storage time is the sum of this param-
eter plus the pre-trigger and the post-fault time. With this parameter set to infinite, the
fault recording runs for as long as the binary input is energized. It cannot, however,
run for longer than the maximum storage time. To set the parameter to infinite, incre-
ment the value for this parameter with the arrow keys until the symbol ”
∞
” appears.
T-KEYBOARD
The parameter
T-KEYBOARD
(
7432/BU
)
is used to set the storage time when fault re-
cording is initiated from the membrane keyboard on the operator panel.
5.13.3 Settings of the Bay Unit
Addr.
Parameters
Setting Options
Default Settings
Comments
7402
INITIATION
STORAGE BY FD.
STORAGE BY TRIP
START WITH TRIP
STORAGE BY
TRIP
Start/storage criterion for fault
recording
7410
T-MAX
0.30 .. 5.00 s
2.00 s
Maximum time period available
for one fault record
7411
T-PRE
0.05 .. 0.50 s
0.20 s
Pre-trigger time for fault record-
ing
7412
T-POST
0.05 .. 0.50 s
0.20 s
Post-fault time for stopping the
fault recording after the fault cri-
terion disappears
7431
T-BINARY IN
0.10 . .5.00 s
infinite
0.40 s
Storage time when fault record-
ing is initiated via a binary input
7432
T-KEYBOARD
0.10 .. 5.00 s
0.40 s
Storage time when fault record-
ing is initiated via the membrane
keyboard
www
. ElectricalPartManuals
. com
Содержание SIPROTEC 7SS522 V4.6
Страница 326: ...Maintenance and Repair 310 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 432: ...Appendix 416 7SS52 V4 Manual C53000 G1176 C182 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 438: ...Index 422 7SS52 V4 Manual C53000 G1176 C182 34 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...