Check Zone
113
7SS52 V4 Manual
C53000-G1176-C182-3
Due to the phase angle differences between short-circuit current and load currents dif-
ferences may occur in the formation of the sums.
5.2.2
Setting Notes
The check zone has its own characteristics, which can be set with the parameters
6103/CU
6111A/CU
) and
6110A/CU
5.2.3
Settings for the Central Unit
Addr.
Setting Title
Setting Options
Default Setting
Comments
6103
StAB FAC:CZ
0.00 .. 0.80
0.50
Stabilizing factor check zone
6104
Id> CZ
0.20 .. 4.00 I/Ino
1.00 I/Ino
Diff-current threshold - check
zone
6110A
Is< CZ - EF
0.00 .. 25.00 I/Ino
4.50 I/Ino
Stabilizing current threshold - CZ
- EF
6111A
Id> CZ - EF
0.05 .. 4.00 I/Ino
0.25 I/Ino
Diff-current threshold - check
zone - EF