Technical Data
10-34
7SJ63 Manual
C53000-G1140-C120-1
10.14 Breaker Failure Protection (50BF)
Pickup and Time
Delay Ranges/
Resolutions
Pickup of 50 Element BkrClosed
I
MIN 0.20 A to 5.00 A
1
) (Increments 0.05 A)
1
)
Time Delay
TRIP-Timer
0.06 s to 60.00 s (Increments 0.01 s)
or
∞ (
no trip)
Initiating Time
Pickup Times (protection initiates)
- For Internal Start
included in time delay
- Using Controls
included in time delay
- For External Start
included in time delay
Reset Time
approx. 25 ms
Tolerances
Pickup Current
BkrClosed I MIN3% of set value, or 50 mA
1
)
Time Delay
TRIP-Timer
1% or 20 ms
Influencing Vari-
ables
Power supply DC voltage (V
DC
) in range
0.8
≤
V
PS
/ V
PS nominal
≤
1.15
1%
Temperature in range
23º F
≤
ϑ
amb
≤
131º F
0.3 % /10º F
Frequency in range
0.95
≤
f/f
N
≤
1.05
1%
Harmonics
- Up to 10% 3
rd
harmonic
1%
- Up to 10% 5
th
harmonic
1%
1
) For I
N
= 1A, divide all limits by 5.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SJ63
Страница 16: ...xiv 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 28: ...Introduction 1 12 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 112: ...SIPROTEC 4 Devices 4 38 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 346: ...Functions 6 182 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 494: ...Technical Data 10 48 7SJ63 Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 604: ...Index Index 6 7SJ63 Instruction Manual C53000 G1140 C120 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...