Technical Data
4.12 Motor Restart Inhibit 66
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
507
4.12
Motor Restart Inhibit 66
Setting Ranges / Increments
Restart Threshold
Influencing Variables
Motor starting current relative to nominal motor current
I
Start
/
I
Motor Nom.
1.1 to 10.0
Increment 0.1
Nominal motor current
I
Motor Nom.
for
I
Nom
= 1 A 0.20 A to 1.20 A
Increment 0.01 A
for
I
Nom
= 5 A 1.00 A to 6.00 A
Max. permissible starting time T
START max.
3 s to 320 s
Increments 1 s
Equilibrium time T
Equal
0.0 min to 320.0 min
Increments 0.1 min
Minimum inhibit time T
MIN. INHIBIT TIME
0.2 min to 120.0 min
Increments 0.1 min
Maximum permissible number of warm startups n
WARM
1 to 4
Increment 1
Difference between cold and warm startups n
COLD
- n
WARM
1 to 2
Increment 1
Extension of Time Constant at stop k
τ
at STOP
0.2 to 100.0
Increment 0.1
Extension of Time constant at running k
τ
at RUNNING
0.2 to 100.0
Increment 0.1
Where:
Θ
RESTART
= Temperature limit below which restarting is possible
k
R
= k-factor for the rotor
I
STARTUP
= Startup current
I
MotNom
= Motor nominal current
T
start max
= Max. startup time
τ
R
= Thermal rotor time constant
n
cold
= Max. number of cold starts
Power supply direct voltage in range 0.8
≤
V
PS
/V
PSNom
≤
1.15
1 %
Temperature in range 23.00 °F (-5 °C)
≤
Θ
amb
≤
131.00 °F (55 °C)
0.5 %/10 K
Frequency in range f
Nom
±
5 Hz
1 %
Frequency outside range f
Nom
±
5 Hz
Increased Tolerances