Technical Data
4.1 General Device Data
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
471
Additional Interface (only 7SJ64)
System Interface
Connection
isolated interface for data transfer with RTD-
boxes
Transmission Speed
min. 4,800 Baud; max. 115,200 Baud;
Factory setting 38,400 Baud
RS485
Connection for flush-mounted casing rear panel, mounting location „D“,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing bottom;
shielded data cable
Test Voltage
500 VAC
Maximum Distance of Transmission
3,280 feet (1,000 m)
Fiber Optical Link (FO)
FO connector type
ST connector
Connection for flush-mounted casing Rear panel, mounting location „D“
Connection for surface-mounted
casing
at the housing mounted case on the case
bottom
Optical Wavelength
λ
= 820 nm
Laser Class 1 according to
EN 60825-1/-2
using glass fiber 50/125 µm or using glass
fiber 62.5/125 µm
Permissible Optical Link Signal Atten-
uation
max. 8 dB, with glass fiber 62.5/125 µm
Maximum Distance of Transmission
max. 0.93 miles (1.5 km)
Character Idle State
Configurable: factory setting „Light off“
IEC 60870-5-103
single
RS232/RS485/FO according to the
ordering variant
isolated interface for data transfer to a
master terminal
RS232
Connection for flush-mounted casing rear panel, mounting location „B“,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing mounted case on the case
bottom
Test Voltage
500 VAC
Transmission Speed
min. 1,200 baud, max. 115,200 baud;
Factory setting 9,600 baud
Maximum Distance of Transmission
49.2 feet (15 m)
RS485
Connection for flush-mounted casing rear panel, mounting location „B“,
9-pole D-SUB miniature female connector
Connection for surface-mounted
casing
at the housing mounted case on the case
bottom
Test Voltage
500 VAC
Transmission Speed
min. 1,200 baud, max. 115,200 baud;
Factory setting 9,600 baud
Maximum Distance of Transmission
max. 0.62 miles (1 km)
www
. ElectricalPartManuals