Functions
2.1 General
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
41
Default Display Selection
In devices with 4-line displays and depending on the device version, a number of predefined image pages are
available. The start page of the default display appearing after startup of the device can be selected in the
device data via parameter
640
Start image DD
. The available image pages are listed in Annex A.5.
2.1.2.3
Settings
2.1.2.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
610
FltDisp.LED/LCD
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
611
Spont. FltDisp.
YES
NO
NO
Spontaneous display of flt.annun-
ciations
640
Start image DD
image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
image 9
image 10
image 1
Start image Default Display
No.
Information
Type of In-
formation
Comments
-
>Light on
SP
>Back Light on
-
Reset LED
IntSP
Reset LED
-
DataStop
IntSP
Stop data transmission
-
Test mode
IntSP
Test mode
-
Feeder gnd
IntSP
Feeder GROUNDED
-
Brk OPENED
IntSP
Breaker OPENED
-
HWTestMod
IntSP
Hardware Test Mode
-
SynchClock
IntSP_Ev
Clock Synchronization
-
Error FMS1
OUT
Error FMS FO 1
-
Error FMS2
OUT
Error FMS FO 2
-
Distur.CFC
OUT
Disturbance CFC
1
Not configured
SP
No Function configured
2
Non Existent
SP
Function Not Available
3
>Time Synch
SP_Ev
>Synchronize Internal Real Time Clock
5
>Reset LED
SP
>Reset LED
15
>Test mode
SP
>Test mode
16
>DataStop
SP
>Stop data transmission
51
Device OK
OUT
Device is Operational and Protecting
52
ProtActive
IntSP
At Least 1 Protection Funct. is Active
55
Reset Device
OUT
Reset Device
56
Initial Start
OUT
Initial Start of Device