Functions
2.7 Negative Sequence Protection 46
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
158
2.7.4
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.7.5
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
4001
FCT 46
OFF
ON
OFF
46 Negative Sequence
Protection
4002
46-1 PICKUP
1A
0.10 .. 3.00 A
0.10 A
46-1 Pickup
5A
0.50 .. 15.00 A
0.50 A
4003
46-1 DELAY
0.00 .. 60.00 sec;
∞
1.50 sec
46-1 Time Delay
4004
46-2 PICKUP
1A
0.10 .. 3.00 A
0.50 A
46-2 Pickup
5A
0.50 .. 15.00 A
2.50 A
4005
46-2 DELAY
0.00 .. 60.00 sec;
∞
1.50 sec
46-2 Time Delay
4006
46 IEC CURVE
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv.
46 IEC Curve
4007
46 ANSI CURVE
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
46 ANSI Curve
4008
46-TOC PICKUP
1A
0.10 .. 2.00 A
0.90 A
46-TOC Pickup
5A
0.50 .. 10.00 A
4.50 A
4009
46-TOC TIMEDIAL
0.50 .. 15.00 ;
∞
5.00
46-TOC Time Dial
4010
46-TOC TIMEDIAL
0.05 .. 3.20 sec;
∞
0.50 sec
46-TOC Time Dial
4011
46-TOC RESET
Instantaneous
Disk Emulation
Instantaneous
46-TOC Drop Out
4012A
46 T DROP-OUT
0.00 .. 60.00 sec
0.00 sec
46 Drop-Out Time Delay
No.
Information
Type of In-
formation
Comments
5143
>BLOCK 46
SP
>BLOCK 46
5151
46 OFF
OUT
46 switched OFF
5152
46 BLOCKED
OUT
46 is BLOCKED
5153
46 ACTIVE
OUT
46 is ACTIVE
5159
46-2 picked up
OUT
46-2 picked up
5165
46-1 picked up
OUT
46-1 picked up
5166
46-TOC pickedup
OUT
46-TOC picked up
5170
46 TRIP
OUT
46 TRIP
5171
46 Dsk pickedup
OUT
46 Disk emulation picked up