Functions
2.6 Voltage Protection 27, 59
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
150
2.6.6
Information List
5103
27-1 PICKUP
10 .. 120 V
75 V
27-1 Pickup
5106
27-1 DELAY
0.00 .. 100.00 sec;
∞
1.50 sec
27-1 Time Delay
5110
27-2 PICKUP
10 .. 210 V
70 V
27-2 Pickup
5111
27-2 PICKUP
10 .. 120 V
70 V
27-2 Pickup
5112
27-2 DELAY
0.00 .. 100.00 sec;
∞
0.50 sec
27-2 Time Delay
5113A
27-1 DOUT RATIO
1.01 .. 3.00
1.20
27-1 Dropout Ratio
5114A
27-2 DOUT RATIO
1.01 .. 3.00
1.20
27-2 Dropout Ratio
5120A
CURRENT SUPERV.
OFF
ON
ON
Current Supervision
No.
Information
Type of In-
formation
Comments
234.2100 27, 59 blk
IntSP
27, 59 blocked via operation
6503
>BLOCK 27
SP
>BLOCK 27 undervoltage protection
6505
>27 I SUPRVSN
SP
>27-Switch current supervision ON
6506
>BLOCK 27-1
SP
>BLOCK 27-1 Undervoltage protection
6508
>BLOCK 27-2
SP
>BLOCK 27-2 Undervoltage protection
6513
>BLOCK 59
SP
>BLOCK 59 overvoltage protection
6530
27 OFF
OUT
27 Undervoltage protection switched OFF
6531
27 BLOCKED
OUT
27 Undervoltage protection is BLOCKED
6532
27 ACTIVE
OUT
27 Undervoltage protection is ACTIVE
6533
27-1 picked up
OUT
27-1 Undervoltage picked up
6534
27-1 PU CS
OUT
27-1 Undervoltage PICKUP w/curr. superv
6537
27-2 picked up
OUT
27-2 Undervoltage picked up
6538
27-2 PU CS
OUT
27-2 Undervoltage PICKUP w/curr. superv
6539
27-1 TRIP
OUT
27-1 Undervoltage TRIP
6540
27-2 TRIP
OUT
27-2 Undervoltage TRIP
6565
59 OFF
OUT
59-Overvoltage protection switched OFF
6566
59 BLOCKED
OUT
59-Overvoltage protection is BLOCKED
6567
59 ACTIVE
OUT
59-Overvoltage protection is ACTIVE
6568
59-1 picked up
OUT
59 picked up
6570
59-1 TRIP
OUT
59 TRIP
6571
59-2 picked up
OUT
59-2 Overvoltage V>> picked up
6573
59-2 TRIP
OUT
59-2 Overvoltage V>> TRIP
Addr.
Parameter
Setting Options
Default Setting
Comments