Technical Data
4.20 Additional Functions
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
364
Group Switchover of the Function Parameters
IEC 61850 GOOSE (inter-relay communication)
Number of Available Setting Groups
4 (parameter group A, B, C and D)
Switchover Performed
Using the keypad
DIGSI using the front PC port
with protocol via system (SCADA) interface
Binary Input
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking The runtime of
GOOSE messages with the protection relay picked up depends on the number of connected IEC 61850 cli-
ents.
As from version V4.6 of the devices, applications with protective functions have to be checked with regard to
their required runtime. In individual cases, the manufacturer has to be consulted with regard to the require-
ments to ensure that the application functions safely.