Technical Data
4.5 DynamiC Cold Load Pickup
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
332
4.5
DynamiC Cold Load Pickup
Timed Changeover of Settings
Setting Ranges / Increments
Controlled Elements
Time overcurrent protection elements (separate phase and ground set-
tings)
Initiation Criteria
Current Criterion
BkrClosed I MIN
Interrogation on the circuit breaker position
Automatic reclosing function ready
Binary Input
Timing
3 Time Delays
(T
CB Open
, T
Active
, T
Stop
)
Current Control
Current threshold "BkrClosed I MIN"
(reset on current falling below threshold: monitoring with timer)
Current Control
„BkrClosed
I
MIN“
for
I
Nom
= 1 A 0.04 A to 1.00 A
Increments 0.01 A
for
I
Nom
= 5 A 0.20 A to 5.00 A
Time Until Changeover To Dynamic
Settings T
CB OPEN
0 s to 21600 s (= 6 h)
Increments 1 s
Period Dynamic Settings are Effective
After a Reclosure T
Active
1 s to 21600 s (= 6 h)
Increments 1 s
Fast Reset Time T
Stop
1 s to 600 s (= 10 min) or
∞
(fast reset inactive) Increments 1 s
Dynamic Settings of Pickup Currents and
Time Delays or Time Multipliers
Adjustable within the same ranges and with the same increments
as the directional and non-directional time overcurrent protection
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...