Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
301
3.3.10
Trip/Close Tests for the Configured Operating Devices
Control by Local Command
If the configured operating devices were not switched sufficiently in the hardware test already described, all
configured switching devices must be switched on and off from the device via the integrated control element.
The feedback information of the circuit breaker position injected via binary inputs is read out at the device and
compared with the actual breaker position.
The switching procedure is described in the SIPROTEC 4 System Description. The switching authority must
be set according to the command source used. The switching mode can be selected from interlocked and non-
interlocked switching. Please note that non-interlocked switching can be a safety hazard.
Control by Protective Functions
For OPEN-commands sent to the circuit breaker please take into consideration that if the internal or external
automatic reclosure function is used a TRIP-CLOSE test cycle is initiated.
DANGER!
A test cycle successfully started by the automatic reclosure function can lead to the closing of the
circuit breaker !
Non-observance of the following statement will result in death, severe personal injury or substantial property
damage.
Be fully aware that OPEN-commands sent to the circuit breaker can result in a trip-close-trip event of the circuit
breaker by an external reclosing device.
Control from a Remote Control Center
If the device is connected to a remote substation via a system interface, the corresponding switching tests may
also be checked from the substation. Please also take into consideration that the switching authority is set in
correspondence with the source of commands used.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...