Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
258
3.1
Mounting and Connections
General
WARNING!
Warning of improper transport, storage, installation or assembly of the device.
Failure to observe these precautions can result in death, personal injury, or serious material damage.
Trouble-free and safe use of this device depends on proper transport, storage, installation, and assembly of
the device according to the warnings in this device manual.
Of particular importance are the general installation and safety regulations for work in a high-voltage environ-
ment (for example, ANSI, IEC, EN, DIN, or other national and international regulations). These regulations must
be observed.
3.1.1
Configuration Information
Prerequisites
For installation and connections the following requirements and conditions must be met:
The rated device data has been checked as recommended in the SIPROTEC
®
4 System Description. Their
compliance with the power system data has been verified.
General Diagrams
General diagrams for 7SJ61 are shown in Appendix A.2. Connection examples for current transformer circuits
are provided in A.3.
Binary Inputs and Outputs
The configuration options of the binary in- and outputs, i.e. the procedure for the individual adaptation to the
plant conditions, are described in the SIPROTEC 4 System Description. The connections to the plant are de-
pendent on this configuration. The presettings of the device are listed in Appendix A.5. Please also check that
the labelling strips on the front panel correspond to the configured message functions.
Setting Group Change
If binary inputs are used to switch setting groups, please observe the following:
• Two binary inputs must be dedicated to the purpose of changing setting groups when four groups are to be
switched. One binary input must be set for
„>Set Group Bit0“
, the other input for
„>Set Group Bit1“
.
If either of these input functions is not assigned, then it is considered as not controlled.
• For the control of 2 setting groups one binary input is sufficient, namely
„>Set Group Bit0“
, since the
non-assigned binary input
„>Set Group Bit1“
is then regarded as not not connected.
• The control signals must be permanently active so that the selected setting group is and remains active.
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...