Functions
2.13 Flexible Protection Functions
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
198
2.13.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
Setting Options
Default Setting
Comments
0
FLEXIBLE FUNC.
OFF
ON
Alarm Only
OFF
Flexible Function
0
OPERRAT. MODE
3-phase
1-phase
no reference
3-phase
Mode of Operation
0
MEAS. QUANTITY
Please select
Current
Binary Input
Please select
Selection of Measured Quantity
0
MEAS. METHOD
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental
Selection of Measurement
Method
0
PICKUP WITH
Exceeding
Dropping below
Exceeding
Pickup with
0
CURRENT
Ia
Ib
Ic
In
In sensitive
In2
Ia
Current
0
P.U. THRESHOLD
Pickup Threshold
0
P.U. THRESHOLD
Pickup Threshold
0
P.U. THRESHOLD
0.001 .. 1.500 A
0.100 A
Pickup Threshold
0
P.U. THRESHOLD
15 .. 100 %
20 %
Pickup Threshold
0
T TRIP DELAY
0.00 .. 3600.00 sec
1.00 sec
Trip Time Delay
0
T PICKUP DELAY
0.00 .. 60.00 sec
0.00 sec
Pickup Time Delay
0A
T DROPOUT DELAY
0.00 .. 60.00 sec
0.00 sec
Dropout Time Delay
0A
DROPOUT RATIO
0.70 .. 0.99
0.95
Dropout Ratio
0A
DROPOUT RATIO
1.01 .. 3.00
1.05
Dropout Ratio
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...