Functions
2.8 Monitoring Functions
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
139
2.8.1.6
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.8.1.7
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
8101
MEASURE. SUPERV
OFF
ON
ON
Measurement Supervision
8104
BALANCE I LIMIT
1A
0.10 .. 1.00 A
0.50 A
Current Threshold for
Balance Monitoring
5A
0.50 .. 5.00 A
2.50 A
8105
BAL. FACTOR I
0.10 .. 0.90
0.50
Balance Factor for Current
Monitor
8106
Σ
I THRESHOLD
1A
0.05 .. 2.00 A;
∞
0.10 A
Summated Current Moni-
toring Threshold
5A
0.25 .. 10.00 A;
∞
0.50 A
8107
Σ
I FACTOR
0.00 .. 0.95
0.10
Summated Current Moni-
toring Factor
8109
FAST
Σ
i MONIT
OFF
ON
ON
Fast Summated Current
Monitoring
No.
Information
Type of In-
formation
Comments
161
Fail I Superv.
OUT
Failure: General Current Supervision
162
Failure
Σ
I
OUT
Failure: Current Summation
163
Fail I balance
OUT
Failure: Current Balance
175
Fail Ph. Seq. I
OUT
Failure: Phase Sequence Current
197
MeasSup OFF
OUT
Measurement Supervision is switched OFF
Содержание SIPROTEC 7SJ61
Страница 368: ...Technical Data 4 22 Dimensions SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 368 ...
Страница 436: ...Appendix A 11 Measured Values SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 436 ...
Страница 438: ...Literature SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 438 ...
Страница 450: ...Glossary SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 450 ...
Страница 454: ...Index SIPROTEC 7SJ61 Manual C53000 G1140 C210 1 Release date 02 2008 454 ...