Appendix
A.5 Default Settings
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
351
A.5
Default Settings
A.5.1
LEDs
Table A-3
Preset LED displays
A.5.2
Binary Input
Table A-4
Binary input presettings for all devices and ordering variants
LEDs
Default function
Function No.
Description
LED1
Relay TRIP
511
Relay GENERAL TRIP command
LED2
Relay PICKUP ØA
503
Relay PICKUP Phase A
LED3
Relay PICKUP ØB
504
Relay PICKUP Phase B
LED4
Relay PICKUP ØC
505
Relay PICKUP Phase C
LED5
Relay PICKUP G
506
Relay PICKUP GROUND
LED6
87(N)L Gen.TRIP
32125
87(N)L General TRIP
85 DT Gen. TRIP
3517
85 DT: General TRIP
LED7
Emer. mode
2054
Emergency mode
LED8
Alarm Sum Event
160
Alarm Summary Event
Failure
Σ
i
289
Alarm: Current summation supervision
Binary Input
Default function
Function No.
Description
BI1
>85 DT 3pol
3504
>86 DT: >Intertrip 3 pole signal input
BI2
>87L block
32100
>87L Protection blocking signal
>87N L block
32120
>87N L Protection blocking signal
BI3
>BLOCK 50-STUB
7130
>BLOCK 50-STUB
>BLOCK 50N-STUB
7132
>BLOCK 50N-STUB
BI4
>Rem. Signal 1
3549
>Remote Signal 1 input
BI5
>52a 3p Closed
379
>52a Bkr. aux. contact (3pole closed)
>52a Bkr1 3p Cl
410
>52a Bkr1 aux. 3pClosed (for AR,CB-Test)
BI6
>52b 3p Open
380
>52b Bkr. aux. contact (3pole open)
>52b Bkr1 3p Op
411
>52b Bkr1 aux. 3p Open (for AR,CB-Test)
BI7
>Manual Close
356
>Manual close signal