Functions
2.17 Additional Functions
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
207
Table 2-12
Measured values constellation for device 1
2.17.6
Min/Max Measurement Setup
Minimum and maximum values are calculated by the 7SD80. Time and date of the last update of the values
can also be read out.
2.17.6.1 Description
Minimum and Maximum Values
The minimum and maximum values for the three phase currents
I
x
, the three phase voltages V
x-N
, the phase-
to-phase voltages V
xy
, the positive sequence component
I
1
and V
1
, the active power P, reactive power Q, and
apparent power S, the frequency, and the power factor cos
ϕ
a formed as primary values including the date
and time they were last updated.
The minimum and maximum values of the long-term mean values listed in the next section are also calculated.
The minimum and maximum values can be reset at any time via binary inputs or by using the integrated control
panel or the DIGSI software. Additionally, the reset can be carried out cyclically, starting at a preset point of
time.
2.17.6.2 Setting Notes
Minimum and Maximum Values
The minimum and maximum values can be reset automatically at a programmable point in time. This feature
can be activated by setting address
2811
MinMax cycRESET
to
YES
.
At address
2812
MiMa RESET TIME
you can define the point of time when resetting takes place (minute of
the day).
Address
2813
MiMa RESETCYCLE
allows you to define the resetting cycle (in days).
At address
2814
MinMaxRES.START
you can define when the cyclic process of forming the minimum and
maximum values begins (in days, counted from the time of parameterization).
No.
Information
Type of In-
formation
Comments
7761
„Relay ID“
MV
Device address of the device
7762
„I A_opN=“
MV
I
A (% of nominal operational current)
7763
„
Φ
I A=“
MV
Angle
I
A_remote <->
I
A_local
7764
„I B_opN=“
MV
I
B (% of nominal operational current)
7765
„
Φ
I B=“
MV
Angle
I
B_remote <->
I
B_local
7766
„I C_opN=“
MV
I
C (% of nominal operational current)
7767
„
Φ
I C=“
MV
Angle
I
C_remote <->
I
C_local
7769
„V A_opN=“
MV
VA (% of nominal operational voltage)
7770
„
Φ
V A=“
MV
Angle VA_remote <-> VA_local
7771
„V B_opN=“
MV
VB (% of nominal operational voltage)
7772
„
Φ
V C=“
MV
Angle VB_remote <-> VB_local
7773
„V C_opN=“
MV
VC (% of nominal operational voltage)
7774
„
Φ
V C=“
MV
Angle VC_remote <-> VC_local