Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SD610, Manual
C53000-G1176-C145-6, Release date 02.2011
288
Figure 3-13
Installing a device in a rack or cubicle (housing size
1
/
3
)
3.1.3.3
Panel Mounting
For mounting proceed as follows:
• Secure the device to the panel with four screws. For dimensions see the Technical Data in Section 4.17.
• Connect the low-resistance operational and protective earth to the ground terminal of the device. The cross-
sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor
connected to the device. It must thus be at least 2.5 mm
2
.
• Alternatively, there is the possibility to connect the aforementioned earthing to the lateral earthing surface
with at least one M4 screw.
• Make the connections according to the circuit diagram via screw terminals, connections for optical fibres and
electrical communication modules via the console housings. The specifications concerning the maximum
cross-section, tightening torques, bending radii and strain relief given in the SIPROTEC 4 System Descrip-
tion must be observed. Installation notes are also given in the brief reference booklet that comes with the
device.
Содержание SIPROTEC 7SD610
Страница 16: ...Contents SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 16 ...
Страница 267: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 267 ...
Страница 268: ...Functions 2 18 Command Processing SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 268 ...
Страница 428: ...Appendix A 10 Measured Values SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 428 ...
Страница 430: ...Literature SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 430 ...
Страница 442: ...Glossary SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 442 ...
Страница 448: ...Index SIPROTEC 7SD610 Manual C53000 G1176 C145 6 Release date 02 2011 448 ...